Alarm Standby When polled 0.17 mA (5 mA with LED on) 0.17 mA 22 mA ± 20%
Operating voltage (SLC loop) 24 VDC to 41 VDC
Maximum allowable line resistance 50 Ω
Protection category IP 42
Relative Humidity < 95% (non‑condensing)
Installation temperature +32°F to +100°F (0°C to +38°C) If the sensitivity temperature is programmed within a range of +175°F to +249°F (+79.4°C to +120.6°C), the maximum installation temperature is +150°F (+66°C).
Storage temperature -13°F to +176°F (-25°C to +80°C)
Dimensions (Ø x H) 4.4 in. x 2.0 in. (11.2 cm x 5.1 cm)
Housing Material: CYCOLOY/ABS
Airflow: 4000 ft/min (20 m/s) maximum
Sensitivity: +135°F to +194°F (+57°C to +90°C), programmable + RoR

Parts included with this product

Quantity Component
1 FAH-440 Analog heat head
1 Dust cover