Fire panel, 4-zone 24V, red enclosure

Commercial Type No. FPD-7024
Product No. F.01U.008.460

Line impedance for ground fault detection (Option Bus, conventional input, NAC, secondary power circuit, MUX Bus, AUX power, SMK power) 10 kΩ or less
Power (non-resettable Input) 120 V 60 Hz 1.4 A or 230/240 V 50 Hz, 0.7 A
Power (non‑resettable Auxiliary) 17 to 31 VRMS, unfiltered, 1.0 A
Power (resettable Smoke)1 20.4 to 28.2 VDC nominal, filtered, 1.0 A.
Power (Option Bus) 12 VDC nominal, 500 mA
Power (Notification Appliance Circuit [NAC])2 Each NAC has 24 VRMS nominal, unfiltered power with up to 2.5 A capacity (but limited by the panel’s overall 4.0 A capacity)
Power (Optional Standby Batteries) Two 12 V (in series), 7 Ah to 40 Ah
NACs Line Impedance (voltage loss) 1.5 V
Recommended battery manufacturers3 Power Sonic: PS-1270, PS-12170, PS-12180YUASA: NP7-12, NPG18-12
Temperature (operating and storage) +32°F to +120°F (0°C to +49°C)
Local (on-board) The main control panel includes Three Form C relays. The relay contacts are rated at 5 A, 28 VDC. No over current limiting is performed on the contacts of the relays. The default selection for the relays is to indicate general alarm (relay 1), general system trouble (relay 2), and supervisory (relay 3). By using point or zone mapping, they can be programmed to activate in a wide variety of conditions.
Remote4 Eight Form C relay outputs are provided by a D7035 Remote Relay Module. The module connects to the FACP through the option bus. The outputs are fully programmable, exactly as the local relays are programmed. Each output operates independently of the other seven to provide complete flexibility. Communication with the D7035 is supervised. Contact Rating: 5 A at 28 VDCNumber of Modules: two modules maximum.
Wiring Class B or Class A
Notification patterns Configurable for steady, pulsing, California March, Temporal (ANSI) code 3, synchronized Wheelock, synchronized Gentex, and synchronized System Sensor.

Ethernet Communication Module

Commercial Type No. B426
Product No. F.01U.324.383

Supports two-way communications over Ethernet networks for compatible control panels

Plug-in Communicator Interface

Commercial Type No. B450
Product No. F.01U.323.797

Supports two-way IP communications using plug-in cellular communicators for compatible control panels

Battery, 12V 7Ah

Commercial Type No. D126
Product No. 4.998.125.825

A rechargeable sealed lead‑acid power supply used as a secondary power supply or in auxiliary or ancillary functions.

Annunciator, 8 alarm LED

Commercial Type No. D7030X
Product No. 4.998.800.536

Eight zone LEDs indicate alarm conditions.

Annunciator, 8 LED (2 supervisory)

Commercial Type No. D7030X-S2
Product No. 4.998.140.386

Two LEDs indicate supervisory conditions, six indicate alarm conditions.

Annunciator, 8 LED (8 supervisory)

Commercial Type No. D7030X-S8
Product No. 4.998.140.387

All eight zone LEDs (yellow) indicate supervisory conditions.

Annunciator expander, 8 LED

Commercial Type No. D7032
Product No. 4.998.140.388

Use with D7030X Family LED annunciators

Multiplex octal relay module

Commercial Type No. D7035
Product No. 4.998.800.539

Provide eight Form C relay outputs (w/o enclosure) for the D7024, FPD-7024, or FPA‑1000 Fire Alarm Control Panels (FACP)

Multiplex octal relay module + enclosure

Commercial Type No. D7035B
Product No. 4.998.800.540

Provide eight Form C relay outputs (with enclosure) for the D7024, FPD-7024, or FPA‑1000 Fire Alarm Control Panels (FACP)

Discontinued

Multiplex expansion module

Commercial Type No. D7039
Product No. 4.998.800.529

The D7039 enhances the conventional features of the D7024 or FPD‑7024 FACPs by increasing the number of addressable points to 256, the number of relay outputs to 58 on the D7024 or 59 on FPD‑7024, the number of events on the history buffer to 499, and the number of users to 100.

Remote module, 8-input class B

Commercial Type No. D7042
Product No. 4.998.800.552

Board and plastic enclosure with spring tamper

Multiplex module, metal, 8-input

Commercial Type No. D7042B
Product No. 4.998.140.390

Board on mounting plate with metal enclosure

Multiplex single-input module, 12V

Commercial Type No. D7044
Product No. 4.998.800.545

The module connects a normally‑open (NO) contact to the multiplex bus of an FPD‑7024, D7024, or DS9400 FACP. The module draws supervised input power from the FACP for use in a Class B configuration. Rotary switches allow convenient address setting.

Multiplex mini single-input module, 12V

Commercial Type No. D7044M
Product No. 4.998.800.546

Connects a normally‑open (NO) contact to the multiplex bus of an FPD‑7024, D7024, or DS9400M FACPs.

Multiplex smoke head

Commercial Type No. D7050
Product No. 4.998.140.391

The symmetry of the D7050’s optical chamber allows 360° uniform smoke entry, but minimizes external light entry. Within the chamber, large smoke particles scatter infrared light which is detected by a gated, high-speed, photodiode sensor.

Multiplex detector head, fixed heat

Commercial Type No. D7050TH
Product No. 4.998.140.394

The D7050TH has an optical smoke chamber and a 35°F (57°C) fixed-temperature sensor. Use it in confined areas where a fire increases air temperature slowly but substantially before the fire breaks confinement.

Multiplex base, 2-wire

Commercial Type No. D7050-B6
Product No. 4.998.140.392

Required base for the D7050 and D7050TH MUX smoke heads

Multiplex dual-input module, 12V

Commercial Type No. D7052
Product No. 4.998.800.549

Connects normally‑open (NO) contacts to the multiplex bus of an FPD‑7024, D7024, or DS9400M FACP

Multiplex input/output module, 12V

Commercial Type No. D7053
Product No. 4.998.800.550

Connects normally‑open (NO) contacts to the multiplex bus of an FPD‑7024, D7024, or DS9400M FACP in configures as either Class A or Class B configuration

USB/serial interface module

Commercial Type No. DX4010V2
Product No. F.01U.080.969

Provides a local connection between compatible control panels and approved applications.

Multiplex manual station, single, red

Commercial Type No. FMM-7045
Product No. F.01U.001.461

The single‑action manual station is UL listed and meets Americans with Disabilities Act (ADA) requirements. An address on the polling circuit is easily set with rotary switches. The pull-down handle locks in the activated position. It is reset by opening the unit with a key and then relocking it.

LCD annunciator and control keypad

Commercial Type No. FMR-7033
Product No. F.01U.009.157

Combines remote annunciator and controller functions for fire alarm systems controlled by an FPD‑7024 Fire Alarm Control Panel

LCD annunciator keypad

Commercial Type No. FMR-7036
Product No. F.01U.009.156

Four‑wire LCD annunciator keypad used with the FPD‑7024 Fire Alarm Control Panel to establish the location of a fire alarm

IDC expander, 4-point

Commercial Type No. FPC-7034
Product No. F.01U.003.861

The FPC‑7034 adds four Class B (Style B) or two Class A (Style D) initiating circuits to the FPD‑7024 FACP. This plug‑in module is automatically recognized by the control panel's firmware when power is restored to the system.

Multiplex expansion module for FPD-7024

Commercial Type No. FPE-7039
Product No. F.01U.299.029

It enhances the features of the FACPs. It increases the number of addressable points to 247. It increases the number of relay outputs to 58 on the D7024/DS9400 or 59 on the FPD‑7024. It increases number of events on the history buffer to 499.

Power supply, RNAC 8A 24V

Commercial Type No. FPP-RNAC-8A-4C
Product No. F.01U.003.444

When connected to a panel’s option bus, the FPP-RNAC-8A-4C adds four additional NFPA 72, Class B or Class A NACs. When connected directly to the NAC output, it is also a NAC power supply for fire-protective signaling systems.

Discontinued

GPRS/GSM integrated communicator

Commercial Type No. ITS-DX4020-G
Product No. F.01U.082.094

Digital cellular communicator used for two-way IP or dialed communications over GPRS/GSM networks.

Title Type Language
Title
CSFM
Type
PDF
Language
Title
FCC
Type
PDF
Language
Title
FDNY-CoA
Type
PDF
Language
Title
FM
Type
PDF
Language
Title
UL
Type
PDF
Language
en-US 
Title
CAD Drawing DWG (FPD-7024)
Type
DWG
Language
en-US 
Title
Commercial Brochure
Type
PDF
Language
en-US 
Title
Datasheet (FPD-7024)
Type
PDF
Language
en-US 
Title
Installation manual
Type
PDF
Language
en-US  es-AR 
Title
Program Record Sheet
Type
PDF
Language
en-US  es-AR  pt-BR 
Title
Quick Selection Guide
Type
PDF
Language
en-US 
Title
Release notes
Type
PDF
Language
en-US 
Title
Special (- Smoke Detector Compatibility List)
Type
PDF
Language
en-US 
Title
Special (FPD-7024_ElecDocDownloads)
Type
PDF
Language
en-US  es-AR  pt-BR 
Title
Special (NAC Compatibility List)
Type
PDF
Language
en-US 
Title
Special (Operating instruction sheet)
Type
PDF
Language
en-US  pt-BR  es-ES 
Title
Special (Technical Bulletin - Product Issues During Installation)
Type
PDF
Language
en-US 
Title
Special (Technical Bulletin - Upgrading to FPD-7024)
Type
PDF
Language
en-US 
Title
Technical bulletin (F01U343343-01_FPD-7024_Translation_Error_TSN)
Type
PDF
Language
en-US  es-AR 
Title
Software (FPD-7024_Battery_Calculator_v1.10.03)
Type
ZIP
Language
en-US 
Title
Software (RPS v6.10.001)
Type
EXE
Language
en-US 
Title
Software (RPS-FPD7024-SP1)
Type
ZIP
Language
en-US  es-ES  fr-FR 
forward-right_adjusted