Duct smoke detector
CTN: FCD-350 | Ürün No F.01U.397.735Anahtar Özellikler
Dimensions (H x W x D) (cm) | 24.13 cm x 19.05 cm x 6.35 cm | |||
Dimensions (H x W x D) (in) | 9.50 in x 7.50 in x 2.50 in | |||
Weight (lb) | 3 lb | |||
Detector head type | Convential photoelectric | |||
Housing material | 18 G.A. steel backbox, clear plastic cover | |||
Sampling tubes | 2.5 ft, 5 ft or 10 ft | |||
Visual indicators | PILOT: Green - Normal | Off - Shutoff/Detector missing ALARM: Off - Normal | Yellow - Check voltage/Detector head | Red - Alarm |
Material | Plastic (ABS) | |||
Color (RAL) | RAL 1014 Ivory |
Operating temperature | Inside duct: 0°C (32°F) ~ 38°C (100°F) Housing ambient: 0°C (32°F) ~ 49°C(120°F) |
Storage temperature (°C) | -30 °C – 70 °C |
Ambient temperature | 0°C (32°F) - 38°C (100°F |
Operating relative humidity, non-condensing (%) | 10% – 93% |
Usage | Indoor/Dry |
Air velocity | 1000 - 4000 ft/min. |
Sensitivity | 1.36-2.33%/FT @ 4000FPM |
Input voltage | Alarm: 24 VDC, 78 mA | 24 VAC, 370 mA | 115 AC, 48 mA | 230 VAC, 31 mA Normal standby : 24VDC 20mA | 24VAC 263mA | 115AC 15mA | 230VAC 10mA |
Standby current | 20 mA @ 24 VDC | ||||||
Alarm current | 78 mA @ 24 VDC | ||||||
Alarm contacts | 2 form C rated 10A @ 115/230 VAC, 7A @ 28 VDC |
Bu ürünlerle birlikte verilen parçalar
Quantity | Component |
---|---|
1 | Detector |
1 | Hardware pack |
1 | Installation guide |