Analog heat detector head, fixed/ROR
Commercial Product No.: FAH-440 | Product No.: F.01U.163.842Alarm Standby When polled | 0.17 mA (5 mA with LED on) 0.17 mA 22 mA ± 20% |
Operating voltage (SLC loop) | 24Â VDC to 41Â VDC |
Maximum allowable line resistance | 50 Ω |
Protection category | IPÂ 42 |
Relative Humidity | < 95% (non‑condensing) |
Installation temperature | +32°F to +100°F (0°C to +38°C) If the sensitivity temperature is programmed within a range of +175°F to +249°F (+79.4°C to +120.6°C), the maximum installation temperature is +150°F (+66°C). |
Storage temperature | -13°F to +176°F (-25°C to +80°C) |
Dimensions (Ø x H) | 4.4 in. x 2.0 in. (11.2 cm x 5.1 cm) |
Housing Material: | CYCOLOY/ABS |
Airflow: | 4000Â ft/min (20Â m/s) maximum |
Sensitivity: | +135°F to +194°F (+57°C to +90°C), programmable + RoR |
Parts included with this product
Quantity | Component |
---|---|
1 | FAH-440 Analog heat head |
1 | Dust cover |