Beam smoke, reflective
Commercial Product No.: FIRERAY5000-UL | Product No.: F.01U.290.198Operating voltage | 14 V DC to 36 V DC |
• In standby, alarm or trouble (1 detector head) | 5.5 mA |
• In standby, alarm or trouble (2 detector heads) | 8 mA |
• In alignment mode (with 1 or 2 detector heads) | 36mA (HiA) 5.5mA / 8mA (LoA) |
Reset control by power disruption | >Â 5Â s |
Alarm relay (contact load) | 100Â mAÂ @Â 36Â V |
Fault relay (contact load) | 100Â mAÂ @Â 36Â V |
• Alarm | Flashes red every 10 s |
• Fault | Flashes yellow every 10 s |
• Operation | Flashes green every 10 s |
• Detector | 5.3 x 5.3 x 5.3 in (135 x 135 x 135 mm) |
• Prism reflector | 3.9 x 3.9 x 0.4 in (100 x 100 x 10 mm) |
• Control unit | 7.9 x 9.3 x 3.2 in (200 x 235 x 81 mm) |
• Color | Light gray/black |
• Material | C6600, non-flammable |
• Detector | 1.1 lbs (500 g) |
• Prism reflector | 0.22 lbs (100 g) |
• Control unit | 2.2 lbs (1000 g) |
Protection class as per ENÂ 60529 | IPÂ 54 |
Permissible operating temperature | -22°F to 131°F (-20°C to 55°C) |

Extension kit, long-range
CTN FRAY5000-LR-KIT
Product No. F.01U.083.264
3 additional prisms for Fireray5000-EN and Fireray5000-UL, for ranges between 164Â ft and 328Â ft (50Â m and 100Â m)

Universal bracket
CTN FRAY5000-BR
Product No. F.01U.098.240
universal bracket for Fireray5000 detector head or prism plate (FRAY5000-1PRISM or FRAY5000-4PRISM)

Prism plate, 1 prism
CTN FRAY5000-1PRISM
Product No. F.01U.098.242
prism plate for 1 prism, for use with universal bracket FRAY5000-BR

Prism plate, 4 prisms
CTN FRAY5000-4PRISM
Product No. F.01U.098.241
prism plate for 4 prisms, for use with universal bracket FRAY5000-BR

Detector backbox
CTN FRAY5000-DETBOX
Product No. F.01U.098.245
Detector Back Box for FRay5000-50-UL Reflective Beam Smoke Detector. Requires FRAY5000-PLATE Cover Plate (sold separately, not available in APR).

Controller back box
CTN FRAY5000-CTRBOX
Product No. F.01U.098.243
FRay-5000 Reflective Beam Detector Controller Back box with knock-outs (not available in APR).

Trim plate for controller back box
CTN FRAY5000-TRIM
Product No. F.01U.098.244
Semi Flush Trim Plate for use with FRAY5000-CTRBOX Controller Back Box for FRay5000 (sold separately, not available in APR).

Ceiling mount
CTN FRAY5000-CMOUNT
Product No. F.01U.098.247
Ceiling Pendant Mount for FRay5000-50-UL Reflective Beam Smoke Detector prism and FRAY5000-BR Universal Bracket Accessory for FRay5000 (not available in APR).

Additional head, UL application
CTN FRAY5000-HEAD-UL
Product No. F.01U.143.248
additional detector head
Parts included with this product
Quantity | Component |
---|---|
1 | Fireray5000 UL Linear Smoke Detector: compact device with integrated transmitter and receiver |
1 | Reflective prism |
1 | Control unit |
1 | Installation kit |