Skip to content Skip to navigation

Bosch Security and Safety Systems | Latin America

Fire panel, 4-zone, 24V, Anatel, red

Commercial Product No.: FPD-7024-A | Product No.: F.01U.268.902
  • 0in stock
  • Express Shipping is available for products in your cart. (time left:)

Expected delivery:28/11/2017

Key Specifications

Line impedance for ground fault detection (Option Bus, conventional input, NAC, secondary power circuit, MUX Bus, AUX power, SMK power) 10 kΩ or less
Power (Input) 120 V 60 Hz 1.4 A or 230/240 V 50 Hz, 0.7 A
Power (non‑resettable Auxiliary) 17 to 31 VRMS, unfiltered, 1.0 A
Power (resettable Smoke)1 20.4 to 28.2 VDC nominal, filtered, 1.0 A.
Power (Option Bus) 12 VDC nominal, 500 mA
Power (Notification Appliance Circuit [NAC])2 Each NAC has 24 VRMS nominal, unfiltered power with up to 2.5 A capacity (but limited by overall 4.0 A capacity)
Power (Optional Standby Batteries) Two 12 V (in series), 7 Ah to 40 Ah
NACs Line Impedance (voltage loss) 1.5 V
Recommended battery manufacturers3 Power Sonic: PS-1270, PS-12170, PS-12180YUASA: NP7-12, NPG18-12
Temperature (operating and storage) +32°F to +120°F (0°C to +49°C)
Wiring Class B or Class A
Notification patterns Configurable for steady, pulsing, California March, Temporal (ANSI) code 3, synchronized Wheelock, synchronized Gentex, and synchronized System Sensor.
Local (on-board) The main control panel includes Three Form C relays. The relay contacts are rated at 5 A, 28 VDC. No over current limiting is performed on the contacts of the relays. The default selection for the relays is to indicate general alarm (relay 1), general system trouble (relay 2), and supervisory (relay 3). By using point or zone mapping, they can be programmed to activate in a wide variety of conditions.
Remote1 Eight Form C relay outputs are provided by a D7035 Remote Relay Module. The module connects to the FACP through the option bus. The outputs are fully programmable, exactly as the local relays are programmed. Each output operates independently of the other seven to provide complete flexibility. Communication with the D7035 is supervised. Contact Rating: 5 A at 28 VDCNumber of Modules: two units maximum.

Replacement key for D101 lock set

CTN D102
Product No. F.01U.020.510

The D102 is a replacement key for locks stamped with 1358.

12 mths wrty ext Conventional Fire panel

CTN EWE-FPC500-IW
Product No. F.01U.360.735

12 months warranty extension

Parts included with this product

Quantity Component
1 Control board in a static‑resistant bag
1 Enclosure
1 Lock set (D101) with two #1358 (D012) keys
1 Transformer (P/N: F01U033706)
6 2.21 kΩ end-of-line resistors (P/N: F01U034504)
1 Hardware pack
1 Literature pack

Title Type Language
Title
ANATEL
Type
PDF
Language
Title
UL
Type
PDF
Language
Title
CAD Drawing DWG
Type
DWG
Language
en-US 
Title
Datasheet
Type
PDF
Language
en-US  pt-BR 
Title
Installation manual
Type
PDF
Language
en-US  pt-BR 
Title
Program Record Sheet
Type
PDF
Language
en-US  es-AR  pt-BR 
Title
Release notes
Type
PDF
Language
en-US 
Title
Special (- Smoke Detector Compatibility List)
Type
PDF
Language
en-US 
Title
Special (FPD-7024_ElecDocDownloads)
Type
PDF
Language
en-US  es-AR  pt-BR 
Title
Special (NAC Compatibility List)
Type
PDF
Language
en-US 
Title
Special (Operating instruction sheet)
Type
PDF
Language
en-US  pt-BR  es-ES 
Title
Software (FPD-7024_Battery_Calculator_v1.10.03)
Type
ZIP
Language
en-US 
Title
Software (RPS v6.11.001)
Type
EXE
Language
en-US 
Title
Software (RPS-FPD7024-SP1)
Type
ZIP
Language
en-US  es-ES  fr-FR 